Pinchin Environmental Newsletter (PEN #21)

Environmental Compliance for Emergency Power Generators

Tables & Figures

 
Table 1: NPC-205 and NPC-232 Sound Level Limits for
One Hour Leq (dBA) or Llm (dBAI)
Time of Day
Class 1 Area
(Urban)
Class 2 Area
(Suburban)
Class 3 Area*
(Rural)

0700 - 1900

50

50

50

1900 - 2300

47

45

45

2300 - 0700

45

45

45

* within 30 metres of dwelling

 
Table 2: MOE Acoustic Assessment Report Requirements
Emergency Generator
Installed Location
Distance from generator air intake or exhaust louvers, or
exhaust stack, to nearest residential property line( metres)
 

≤ 20m

>20m <100 m

≤ 60m

>60m <100 m

Inside Building
(i.e. penthouse)

AAR

NPC-205

 

 

Outdoors in an Enclosure

 

 

AAR

NPC-205


 

Figure 1:
Acoustic audit is not required if the distance between an internally housed emergency generator and off-property receptor exceeds 20m.

Internal Generator Distance

 

Figure 2:
Acoustic audit is not required if the distance between an outdoor emergency generator (housed in an enclosure) and off-site receptor exceeds 60m.

Outside Generator Distance